Prototipe Sistem Pemantauan Tegangan Drop pada Sel Baterai 110 Vdc berbasis Aplikasi Telegram


  • Asrul Asrul * Mail Universitas Muhammadiyah Parepare, Parepare, Indonesia
  • A. Abd. Jabbar Universitas Muhammadiyah Parepare, Parepare, Indonesia
  • Ashadi Amir Universitas Muhammadiyah Parepare, Parepare, Indonesia
  • (*) Corresponding Author
Keywords: Battery; Substation; Voltage Drop; Telegram

Abstract

Batteries are electrochemical devices as a source of DC voltage that is quite reliable and has high stability, so that the 110 Vdc Battery has a very important role at the substation (GI) to operate the driving motors at the voltage breaker (PMT), disconecting switch (PMS), supply PLC and telecommunication equipment in the SCADA system, as well as protection relays. If the 110 Vdc battery does not work properly, it can result in a major interference with the GI. So to help optimize battery maintenance, it needs an indication tool so that the battery can last a long time and can prevent damage to the battery prematurely. In this study, a voltage drop monitoring and detection system will be designed on 110 Vdc battery cells. The data will be forwarded to the database via the NodeMCU device to be sent to the Telegram application on the smartphone. The test was carried out by compiling 80 battery cells with a voltage of 1.5 volts in series to produce a voltage of 110 Vdc. Test results of the accuracy level of voltage readings achieved an average accuracy of 99.58% with an average difference of 0.42% while the test results of sending voltage data for each group were successfully carried out with excellent response and were able to display data / information on voltage values and conditions in telegram applications.

Downloads

Download data is not yet available.

References

E. Nurtiasih, P. E. Pambudi dan S. Priyambodo, “ANALISA KAPASITAS BATERAI KOMUNIKASI PADA GARDU INDUK 150 KV BANTUL,” Jurnal Elektrikal, vol. 4, no. 2, pp. 46-53, 2017.

W.H. Aas, "KEANDALAN MONITORING TELEKOMUNIKASI DATA MENGGUNAKAN SERAT OPTIK DALAM PENGENDALIAN OPERASI SISTEM TENAGA LISTRIK," Jurnal, Redaksi Tim, Energi & Kelistrikan, vol. 7, no.2, pp. 132-136, 2015.

I. Afandi, R. Hidayat dan I. A. Bangsa, “ANALISIS PENGUJIAN KAPASITAS BATERAI 110 VOLT GROUP 2 (SISTEM 500 KV) GITET MANDIRANCAN,” Power Elektronik : Jurnal Orang Elektro, vol. 10, no. 2, pp. 35-38, 2021.

Ginarsa, I., I. Nrartha, B.M. Agung, "Transmisi Daya Tegangan Tinggi Arus Searah (TTAS) Keuntungan Desain Dan Interaksinya Dengan Sistem Arus Bolak-Balik (AB)." 2020.

Sugianto dan N. Lubis, “Kegagalan Proteksi Pada Gardu Induk 150 kV Akibat Suplai Tegangan DC,” Sinusoida, vol. 19, no. 2, pp. 18-26, 2017.

Prameswari, Dhea Natasya. "ANALISIS KINERJA SISTEM PROTEKSI BERDASARKAN FREKUENSI GANGGUAN DI GARDU INDUK 150 KV PADALARANG BARU". Diss. Universitas Siliwangi, 2022.

PLN, P. T. Buku Pedoman Pemeliharaan Proteksi dan Kontrol Penghantar. Jakarta: PT. PLN, 2014.

B. Rifkyantoro, "RANCANG BANGUN UNIT PENGATUR BEBAN PADA GENSET ATSAMF SEBAGAI BACK-UP ENERGI LISTRIK BERBASIS PLC SCHNEIDER MODICON M221CE16R DENGAN MONITORING ARUS DAN TEGANGAN. Diss. undip, 2018.

A. N. Ihsan, Joko, B. Suprianto dan T. Wrahatnolo, “Analisis dan Efisiensi Kebutuhan Kapasitas Baterai 110 Volt DC Gas Insulated Switchgear (GIS) 150 KV Wonokromo Surabaya,” Jurnal Teknik Elektro, vol. 11, no. 3, pp. 481-488, 2022.

Z. T. D. Reis, W. Handajadi dan P. E. Pambudi, “ANALISIS PENURUNAN KAPASITAS BATERAI 110 VOLT UNIT I DI GI 150 KV KENTUNGAN,” Jurnal Elektrikal, vol. 4, no. 1, pp. 10-20, 2017.

S. Sadi dan Adam, “PEMELIHARAAN BOOSTING DAN UJI KAPASITAS BATERE 110 VDC,” Jurnal Teknik, vol. 4, no. 2, pp. 11-16, 2015.

LPPM, SNEKTI. Prosiding SNEKTI 2021. PROSIDING-SNEKTI, 2021, 2.

PLN, P. T.; MI, JALAN TRUNOJOYO BLOK; BARU, KEBAYORAN. Buku pedoman pemeliharaan sistem supli AC/DC. Jakarta: PT. PLN Persero, 2014.


Bila bermanfaat silahkan share artikel ini

Berikan Komentar Anda terhadap artikel Prototipe Sistem Pemantauan Tegangan Drop pada Sel Baterai 110 Vdc berbasis Aplikasi Telegram

Dimensions Badge
Article History
Submitted: 2022-11-14
Published: 2022-11-30
Abstract View: 619 times
PDF Download: 536 times
Section
Articles